MidiPACK-I ECO

TCAITI-THAITI 131÷155

Cooling capacity: 29.5÷55.2 kW

Heating capacity: 32.4÷58.8 kW

WEBCODE: MDI12

Product benefits

  • Efficient and eco-friendly unit in R32
  • Hot water up to -15°C outdoor air
  • Temperature of the produced water up to 60°C
  • Plug&Play unit with integrated hydraulic module
  • Optional EC fans and inverter-based circulation pump
  • Integrated MASTER/SLAVE control
AdesivoAfP_logo-\\ITRHREPOWEB\Archivio_immagini\LOGHI\adaptive\Etichetta AFplus bianco.tif
  • SoloRaffr_logo
  • PdC_logo
  • Install_EST_logo
  • Eurovent_logo
  • ECA_logo
  • Credit_logoFR

Water chillers and packaged reversible air-cooled heat pumps with axial fans. Series with scroll hermetic compressors, DC Inverter and R32 refrigerant gas.



Construction features

• Compressor: scroll type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed adjustment.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate
• The unit is also complete with:
- outdoor air temperature probe for compensation of the Set-point;
- display of cooling circuit high and low pressure;
- electronic expansion valve;
- Master/Slave control up to 4 units in parallel;
- clock board.


Version

T - High efficiency.


Models

TCAITI: unit designed for cooling only.
THAITI: heat pump unit.


PUMP set up

Pump unit with single or double electric pump, including an automatic actuation pump in standby, complete with expansion tank, air vent valves, safety valve and water side pressure gauge. The pumps are available in low or high pressure head versions, and with INVERTER operation.
TANK&PUMP set up
• Pump unit complete with inertial buffer tank and single or double electric pump, including an automatic actuation pump in standby, complete with expansion tank, air vent valves, safety valve and water side pressure gauge. The pumps are available in low or high pressure head versions, and with INVERTER operation.


Factory fitted accessories

• Pre-painted copper/aluminium coils with hydrophilic treatment or copper/copper.
• Desuperheater.
• 100% heat recovery unit (only TCAITI)
• 3-way diverter valve for domestic hot water production, managed by the adjustment.
• Condensing control with fans with EC motor.
• Base antifreeze heater
• Antifreeze heater for buffer tank and electric pumps
• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Double safety valves.
• Refrigerant leak detector
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Energy parameters measurement.
• Silenced set up.
• Cooling circuit high and low pressure gauges.
• Low water set-point temperature.


Separately supplied accessories

• 3-way valve for the production of domestic hot water, managed by the adjustment.
• Remotely controllable outdoor air temperature probe for compensation of the Set-point.
• Additional electrical resistance for heat pump, managed by the adjustment.
• Rubber anti-vibration mounts.
• Water filter.
• Thermostat with display.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.


TCAITI MODEL
Cooling capacity kW
Absorbed power kW
E.E.R.
THAITI MODEL
Heating capacity kW
Absorbed power kW
C.O.P.
Heating capacity kW
Absorbed power kW
C.O.P
Heating capacity kW
Absorbed power kW
C.O.P.
Cooling capacity kW
E.E.R.
TCAITI-THAITI MODELS
Sound pressure dB(A)
Scroll compressor no.
Circuits no.
Buffer tank water content (TANK&PUMP) l
Standard head pump nominal available head (TCAITI) kPa
Electrical supply V-ph-Hz
DIMENSIONS AND WEIGHT
L - Width mm
H - Height mm
P - Depth mm
TCAITI weight kg
THAITI weight kg
SEASONAL ENERGY PERFORMANCE
TCAITI MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW
SEER  (EN 14825)
ηs,c %
THAITI MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW
SCOP (EN 14825)
ηs %
Energy class
131 140 148 155
30,1 38,7 48 55,2
10,13 13,07 15,84 18,46
2,97 2,96 3,03 2,99
131 140 148 155
32,4 42 53,2 58,8
9,67 12,61 15,88 18,32
3,35 3,33 3,35 3,21
32,9 42,9 53,8 59,5
7,99 10,51 13,03 15,14
4,12 4,08 4,13 3,93
22,8 29,1 36,9 40,9
7,65 10 12,42 14,4
2,98 2,91 2,97 2,84
29,5 38,3 47,1 54
2,88 2,91 2,96 2,91
131 140 148 155
51,5 53,5 54,5 55,5
1-inverter 1-inverter 1-inverter 1-inverter
1 1 1 1
150 150 150 150
129 122 116 110
400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
131 140 148 155
2315 2315 2315 2315
1580 1580 1580 1580
1000 1000 1000 1000
450 470 480 490
470 490 500 510
131 140 148 155
30,1 38,7 48 55,2
4,65 4,82 4,91 4,7
183 190 193 185
30 38 48 54
3,9 3,91 3,95 3,9
153 154 155 153
A++ A++ A++ A++

Data at the following conditions:

Air: 35°C D.B. - Water: 12/7°C.

Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.

Air: 7°C D.B. - 6°C W.B. - Water: 30/35°C.

Air: -7°C D.B. - Water: 30/35°C.

In open field (Q = 2) at 5 m from the unit.

Weight referred to the unit without load and not accessorised.

Performance according to EN 14511.

Low temperature application (7°C)

Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)

In Average climatic conditions, low temperature application (35°C)

Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)