Fan coils with EC motor

YARDY-I EV3

Cooling capacity: 1.9÷8.6 kW

Heating capacity: 2.5÷11.8 kW

WEBCODE: YARI3 ACMEC controls: ACREG

Product benefits

  • Enhanced performance with 4-row coil
  • Consumption reduced by 50% compared to traditional motor
  • Continuous fan speed regulation
  • Quieter operation
  • Better room comfort
Inverter_logo GreenLine_logo
  • IntCert1
  • CE_logo
  • Eurovent_logo

Floor and ceiling fan coil units with cabinet for recessed wall or false ceiling installation



Construction features

• Heat exchanger: with finned coil with left-hand connections reversible to right.
• Centrifugal fan with inverter controlled electronic brushless motor and continuous speed regulation.
• Cabinet version structure: covering cabinet in pre-painted sheet steel complete with regenerable filter, ABS polymer grilles and natural condensate drain pan.
• Recessed version structure: in galvanised sheet steel, complete with natural condensate drain pan and regenerable filter.


Versions

• MVP - Vertical unit with cabinet equipped with lower air inlet and upper delivery for wall mounting installation or with feet on ground.
• MVT - Vertical unit with cabinet equipped with front air inlet and upper outlet for floor installation.
• MXP - Horizontal/vertical unit with cabinet, equipped with lower air inlet and upper delivery, for ceiling installation, wall-mounting or with feet on ground.
• MXT - Horizontal/vertical unit with cabinet, equipped with front air inlet and upper delivery, for ceiling or floor installation.
• IVP - Recessed vertical unit equipped with lower air inlet and upper delivery for wall mounting installation.
• IVF - Recessed vertical unit equipped with lower air inlet and front delivery for wall installation.
• IXP - Horizontal/vertical unit equipped with lower air inlet and upper delivery for false ceiling or recessed wall installation.


Accessories

➔❖Additional water heating coil.
➔❖Electrical resistance.
➔❖2 -way ON/OFF electrovalves for 2 and 4-pipe systems.
➔❖3 -way ON/OFF electrovalves for 2 and 4-pipe systems.
➔❖Auxiliary condensate-drain pan.
➔ Manual damper.
➔ Motorised damper.
➔ Back in view.
➔ Rear closing panel.
➔ Rear closing panel with grille and filter.
➔ Support feet with pipe cover.
➔ Frame with filter (G2) that can be extracted in any direction.
➔ Delivery straight fitting.
➔ 90° delivery and inlet fitting.
➔ Telescopic outlet/inlet fitting.
➔ Inlet grille with filter.
➔ Delivery grille.
➔ Cover panel with grilles (only IXP).
➔ Flanged frame for connection to duct.
➔ Anti-vibration fitting for delivery/inlet duct connection.
➔ Intake/outlet plenum with round nozzles.


STANDARD controls

For wall mounting installation
➔ Electronic panel with display and RS485 serial interface, semi-recessed in wall.


iDRHOSS Controls

➔ Wall mounting receiver for remote control.
➔ Electronic panel for wall mounting or installation on machine.
➔ Wall-mounted recessed electronic panel

For installation on machine
➔❖ Master/slave electronic board, ON/OFF valve control module and electrical resistance, temperature probe for hot row.
➔ RS485 interface for serial communication with other devices (proprietary protocol; Modbus RTU protocol).
➔ RS 485/USB serial converter.
➔ Serial interface (CAN-bus - Controller Area Network) for the iDRHOSS system.
➔ KGTW-BAC- Gateway RS485/BACnet (max 64 fan coil).
➔ KGW-LON - Gateway RS485/FTT10-LonWorks (max 64 fan coil).

Key: ❖ Factory fitted
➔ Supplied separately

YARDY-I EV3 MVP-MVT-MXP-MXT-IVP-IVF-IXP
Total cooling capacity kW
kW
kW
Total cooling capacity [EN1397] kW
kW
kW
Heating capacity (45°C) [EN1397] kW
kW
kW
Heating capacity (50°C) kW
kW
kW
Heating capacity (70°C) [EN1397] kW
kW
kW
Heating capacity of additional coil (65°C) [EN1397] kW
kW
kW
Heating capacity of additional coil (70°C) kW
kW
kW
Air flow speed m³/h
m³/h
m³/h
Sound power dB(A)
dB(A)
dB(A)
Sound pressure dB(A)
dB(A)
dB(A)
Absorbed power W
W
W
Electrical supply V-ph-Hz
DIMENSIONS AND WEIGHTS
L - MXP-MXT-MVP-MVT width mm
L - IVP-IXP-IVF width mm
H - MXP-MXT-MVP-MVT height mm
H - IVP-IXP-IVF height mm
MVP-MVT-MXP-MXT Feet height mm
P - MXP-MXT-MVP-MVT Depth mm
P - IVP-IXP-IVF Depth mm
MXP-MXT-MVP-MVT Weight kg
IVP-IXP-IVF Weight kg
20 24 30 34 45 48 60 74 80 88
1,88 2,25 3 3,4 4,15 4,64 6,37 7,41 8,08 8,55
1,45 1,69 2,33 2,77 3,06 3,49 4,62 5,27 5,92 6,38
0,75 0,81 1,09 1,35 1,54 1,74 1,79 2,11 2,11 2,26
1,86 2,23 2,97 3,37 4,11 4,6 6,28 7,32 7,94 8,4
1,44 1,68 2,32 2,75 3,05 3,48 4,59 5,24 5,87 6,32
0,74 0,8 1,08 1,34 1,53 1,73 1,78 2,1 2,1 2,25
2,09 2,18 3,27 3,41 4,46 4,65 7,13 7,41 9,67 10,07
1,48 1,56 2,52 2,6 3,13 3,27 5,13 5,31 7,15 7,43
0,77 0,81 1,2 1,23 1,51 1,57 1,88 1,94 2,63 2,74
2,47 2,59 3,87 4,06 5,28 5,54 8,38 8,8 11,29 11,77
1,77 1,88 2,99 3,14 3,74 3,93 6,07 6,37 8,39 8,75
0,91 0,96 1,42 1,49 1,81 1,9 2,24 2,35 3,07 3,22
4,2 4,35 6,56 6,83 8,92 9,31 14,28 14,85 19,36 20,15
2,98 3,14 5,06 5,26 6,28 6,56 10,3 10,77 14,35 14,91
1,55 1,62 2,44 2,51 3,06 3,19 3,85 3,96 5,37 5,6
1,95 2,07 2,94 2,8 3,37 3,2 5,63 5,37 6,51 6,16
1,66 1,57 2,34 2,23 2,84 2,71 4,68 4,45 5,4 5,14
0,88 0,83 1,29 1,23 1,54 1,46 2,17 2,06 2,52 2,4
2,19 2,33 3,3 3,14 3,79 3,6 6,29 5,98 7,23 6,83
1,91 1,81 2,63 2,5 3,29 3,13 5,27 5,01 6,07 5,77
1 0,95 1,47 1,4 1,78 1,69 2,49 2,37 2,89 2,75
331 331 523 523 645 645 1235 1235 1503 1458
230 230 400 400 450 450 780 780 965 965
97 97 167 167 198 198 256 256 300 300
48 48 50 50 51 51 62 62 66 66
40 40 43 43 42 42 50 50 56 56
23 23 24 24 25 25 27 27 32 32
39 39 41 41 42 42 53 53 57 57
31 31 34 34 33 33 41 41 47 47
14 14 15 15 16 16 18 18 23 23
23 25 26 28 39 42 89 95 136 146
13 14 15 16 14 15 28 30 52 56
6 6 6 6 7 8 7 7 9 10
230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
20 24 30 34 45 48 60 74 80 88
800 800 1000 1000 1200 1200 1500 1500 1500 1500
550 550 750 750 950 950 1250 1250 1250 1250
570 570 570 570 570 570 570 570 570 570
545 545 545 545 545 545 545 545 545 545
100 100 100 100 100 100 100 100 100 100
220 220 220 220 220 220 220 220 220 220
212 212 212 212 212 212 212 212 212 212
20 20,5 21 22 28 29 35 36 37 38
16,5 17 20,5 21,5 25,5 27 34,5 35,5 36,5 37,5

Data at the following conditions:

Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.

Air: 20°C - Water: 45/40°C.

Air: 20°C - Water: 50°C, flow rate as in cooling.

Air: 20°C - Water: 70/60°C.

Air: 20°C - Water: 65/55°C.

For room volume equal to 100 m³ and reverberation time = 0.5 sec.

E

Eurovent certified performance.

MAX, MED, MIN speed with 10 Vdc, 6 Vdc, 1 Vdc input.

YARDY-I EV3 24 - 34 - 48 - 74 - 88 with oversized 4-row coil.

References

27 March 2017

Al Maktoum Hospital Rd

UNITED ARAB EMIRATES

06 March 2017

Meydan Business Park

UNITED ARAB EMIRATES

20 February 2017

Aster Hospital Al Rafa

UNITED ARAB EMIRATES

25 November 2016

Kent College Dubai

UNITED ARAB EMIRATES

16 May 2016

Energy Park

ITALY