Ductable terminals

YARDY-HP

Cooling capacity: 7.2÷20.5 kW

Heating capacity: 9.6÷28.0 kW

WEBCODE: YAHP1 ACMEC controls: ACREG

Product benefits

  • Horizontal and vertical installation
  • New pan removable from below for cleaning
  • Set up with 3, 4, 5-row coil
  • Filters with different efficiency levels
  • Remote control
  • Canalizabile_logo
  • CE_logo

Ductable terminals for recessed horizontal or vertical installation.



Construction features

• Structure: self-supporting, in galvanised sheet steel for horizontal installation in a false ceiling or vertical recessed wall installation, complete with natural condensate drain pan, flanges to fit to the inlet/delivery duct. Pan is removable from below. Filter supplied separately from the unit.
• Heat exchanger: with finned coil and electrical box for terminal block with reversible left connections, which can be switched right directly on site. Coil is removable from below.
• Double inlet centrifugal fan with directly coupled 3-speed motor. Fan unit is removable from below.


Versions

• CXP - Recessed unit for horizontal or vertical installation (with lower return to upper delivery)


Number of rows

• 3 Rows - Unit with 3-row coil; unit for recessed horizontal/vertical installation.
• 4 Rows - Unit with 4-row coil; unit for recessed horizontal/vertical installation.
• 5 Rows - Unit with 5-row coil (only models 250, 300); unit for recessed horizontal/ vertical installation.


Accessories

➔❖ Additional water heating coil (1 row) for 4T-KBAA 4-pipe systems - only for 3R units with a 3-row coil.
➔ External plenum with additional water heating coil for 4-pipe systems (PBAB).
➔❖ ON/OFF 2-way electrovalves for 2 and 4-pipe-systems.
➔❖ On/OFF 3-way electrovalves for 2 and 4-pipe-systems.
➔❖ Auxiliary condensate drain pan.
➔ Frame with filter that can be extracted in any direction (efficiency rating G1/ G2/G3).
➔ Straight delivery and inlet connection.
➔ 90° delivery and inlet fitting.
➔ Flange for connection to duct.
➔ Anti-vibration connection for connection to the inlet/delivery duct.
➔ Panel with round nozzles to be connected to the delivery/inlet connections.


STANDARD controls

For wall mounting installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, speed switch, ON/OFF valve signal and electrical resistance.
➔ Electronic panel with automatic summer/winter switching for 2-pipe systems.
➔ Electronic panel with automatic summer/winter switching and automatic speed regulation for 2-pipe systems with electrical resistance or 4-pipe systems.
➔ Air probe with remote control option.
➔ Interface card to control up to 4 fan coils (models 100-150-200 only, for on board installation).


iDRHOSS Controls

➔ Wall mounting receiver for remote control.
➔ Electronic panel for wall mounting installation.
➔ Wall-mounted recessed electronic panel

For installation on machine
➔❖ Master/slave electronic board.
➔❖ Temperature probe for hot row.
➔❖ Module for ON/OFF valves and electrical resistance management.
➔ RS485 interface for serial communication with other devices (proprietary protocol; Modbus RTU protocol).
➔ RS 485/USB serial converter.
➔ Serial interface (CAN-bus - Controller Area Network) for the iDRHOSS system.
➔ KGTW-BAC- Gateway RS485/BACnet (max 64 fan coil).
➔ KGW-LON - Gateway RS485/FTT10-LonWorks (max 64 fan coil).

Key: ❖ Factory fitted
➔ Supplied separately

YARDY HP CXP
Total cooling capacity kW
Total cooling capacity [EN1397] kW
Heating capacity (45°C) [EN1397] kW
Heating capacity (50°C) kW
Total cooling capacity kW
Total cooling capacity [EN1397] kW
Heating capacity (45°C) [EN1397] kW
Heating capacity (50°C) kW
Total cooling capacity kW
Total cooling capacity [EN1397] kW
Heating capacity (45°C) [EN1397] kW
Heating capacity (50°C) kW
Heating capacity of additional coil (70°C) kW
Heating capacity of additional coil (65°C) [EN1397] kW
Heating capacity of additional coil (70°C) kW
Heating capacity of additional coil (65°C) [EN1397] kW
Air flow rate/Speed static pressure (3R) m³/h / Pa
m³/h / Pa
m³/h / Pa
Delivery sound power (3R) dB(A)
dB(A)
dB(A)
Speed sound pressure (3R) dB(A)
dB(A)
dB(A)
Nominal spd absorbed power MAX W
W
W
Maximum absorbed power (0 Pa) W
Electrical supply V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width mm
H - Height mm
P - YARDY HP Depth mm
P - PBAB Depth mm
YARDY HP Weight kg
100 150 200 250 300
7,16 8,37 10,13 13,53 15,22
6,96 8,13 9,75 12,85 14,42
8,37 10,22 12,56 17,02 19,5
9,66 11,71 14,28 19,12 21,82
8,41 9,51 11,37 16,55 18,75
8,22 9,28 11,04 15,88 18
9,31 10,92 13,33 19,59 22,61
10,86 12,68 15,38 22,35 25,76
- - - 18,7 20,5
- - - 18,04 19,75
- - - 21,83 24,61
- - - 25,04 28,11
6,69 6,78 9,35 10,44 11,31
6,09 6,22 8,61 9,86 10,74
12,9 14,14 16,4 29,73 32,77
11,56 12,69 14,78 26,92 29,68
1.552 / 60 1.840 / 60 2.339 / 60 3.312 / 60 3.875 / 60
1.369 / 50 1.620 / 50 1.717 / 50 2.189 / 50 3.075 / 50
1.013 / 35 1.432 / 35 1.414 / 35 1.329 / 35 2.415 / 35
61 62 62 63 68
59 61 60 59 64
56 59 57 55 61
47 48 48 49 54
45 47 46 45 50
42 45 43 41 47
200 245 380 680 800
190 230 330 670 750
- - - 660 750
280 300 500 850 900
230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
100 150 200 250 300
1295 1295 1295 1295 1295
250 250 285 335 335
555 555 670 720 720
200 200 200 200 200
38 38 46 57 57

Data at the following conditions:

Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.

Air: 20°C - Water: 45/40°C.

Air: 20°C - Water: 50°C, flow rate as in cooling.

Air: 20°C - Water: 70/60°C.

Air: 20°C - Water: 65/55°C.

3 row coil (3R) without filter.

With G3 filter at the conditions specified in point 6 according to EN16583

At 2 m from the air outflow point with directionality factor 2 and G3 filter.