WinPACK-R SE

TCAEBY-TCAESY 4225÷4345

Cooling capacity: 214.2÷345.7 kW

WEBCODE: WK021

Product benefits

  • Compact chillers also for replacement markets
  • High performance range with extended operating limits
  • Simplified installation thanks to the pumping unit accessories
  • Integrated MASTER/SLAVE control
GreenLine_logo AdesivoAfP_logo
  • SoloRaffr_logo
  • Install_EST_logo
  • R410A_logo
  • CE_logo
  • Eurovent_logo
  • Bureau_Veritas_logo

Packaged air-cooled water chillers with axial fans. Range with scroll hermetic compressors and R410A refrigerant.



Construction features

• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• 4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: with micro-channels.
• Fan: external rotor axial type electric fans with internal thermal protection of accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor circuit breaker switches;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board.


Versions

• B - Standard version.
• S - Silenced version complete with compressor technical compartment soundproofing and reduced speed fans.


Models

• TCAEBY: standard unit designed for cooling only.
• TCAESY: silenced unit designed for cooling only.


Factory fitted accessories

• Shell and tube evaporator.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with integrated 500 - 700 litre buffer tank (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• VPF control.
• Desuperheater.
• 100% heat recovery unit.
• Electronic expansion valve.
• –10°C condensing control (standard in S versions).
• –15°C condensing control with fans with EC motor.
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Soundproofed compressor box.
• Compressor soundproof enclosures.
• Cooling circuit delivery and intake valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Coil protection nets.
• Micro-channel coils with E-coating treatment.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.


Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.


TCAEBY-TCAESY MODEL
Nominal cooling capacity kW
Nominal cooling capacity kW
E.E.R.
E.E.R.
Absorbed power kW
Absorbed power kW
TCAEBY-TCAESY MODEL
Sound pressure dB(A)
Sound pressure dB(A)
Sound power dB(A)
Sound power dB(A)
Scroll/step compressor no.
Circuits no.
Electrical supply V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width mm
H - Height mm
P - Depth mm
TCAEBY weight kg
TCAESY weight kg
SEASONAL ENERGY PERFORMANCE
TCAEBY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW
SEER  (EN 14825)
ηs,c %
TCAESY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW
SEER  (EN 14825)
ηs,c %
4225 4245 4265 4315 4345
220,2 241,2 264 313,9 345,7
214,2 234,2 252,1 305 333,8
3,00 2,81 2,61 2,88 2,81
2,90 2,67 2,4 2,76 2,66
73,4 85,8 101,1 108,9 123,0
73,9 87,7 105,0 110,5 125,5
4225 4245 4265 4315 4345
58 59 60 61 62
52 53 54 56 57
90 91 92 93 94
84 85 86 88 89
4/4 4/4 4/4 4/4 4/4
2 2 2 2 2
400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
4225 4245 4265 4315 4345
2550 2550 2550 3650 3650
2450 2450 2450 2450 2450
2260 2260 2260 2260 2260
1300 1500 1650 1985 2000
1460 1660 1810 2215 2230
4225 4245 4265 4315 4345
220,2 241,2 264,0 313,9 345,7
4,17 4,16 4,14 4,18 4,16
164 163 163 164 163
214,2 234,2 252,1 305,0 333,8
4,15 4,13 4,12 4,15 4,14
163 162 162 163 163

Data at the following conditions:

Air: 35°C - Water: 12/7°C.

In open field (Q = 2) at 10 m from the unit.

Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.

Weight referred to the unit without load and not accessorised.

TCAESY silenced versions

Performance according to EN 14511:2013.

Low temperature application (7°C)