Low consumption Compact-Y SM

THAEY 122÷130

Cooling capacity: 22.7÷29 kW

Heating capacity: 23.5÷34 kW

WEBCODE: CY001

GreenLine_logo AdesivoAfP_logo
  • SoloRaffr_logo
  • PdC_logo
  • Install_EST_logo
  • R410A_logo
  • CE_logo
  • Eurovent_logo
  • Bureau_Veritas_logo

Packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors and R410A refrigerant gas.



Construction features

• Compressor: hermetic, rotary scroll compressor, complete with thermal protection and casing heater for mod. 127÷130.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection and accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: in galvanised and painted steel plate, complete with condensate drain pan.


Models

• THAEY: heat pump unit.


PUMP set up

• Pump unit complete with: circulator or electric circulation pump, membrane expansion tank, manual air vent valve, safety valve and pressure gauge.

TANK & PUMP set up
• Pump unit complete with: inertial buffer tank, circulator or electric circulation pump, membrane expansion tank, manual air vent valve, automatic air vent valve, safety valve, and pressure gauge.


Factory fitted accessories

• Soft-start device.
• Silenced set up.
• –10°C condensing control.
• Antifreeze heater on the buffer tank.
• Compressor casing heater (mod. 122).
• Unit base antifreeze heater for operation in heat pump mode at low outdoor air temperatures.
• Digital input for double set-point
• 4-20 mA analogue signal for shifting set-point.
• Low water set-point temperature.
• Copper/pre-painted aluminium or copper/copper coils.


Separately supplied accessories

• Rubber anti-vibration mounts.
• –10°C condensing control.
• Water filter.
• 3-way valve for the production of domestic hot water.
• Outdoor air temperature probe for set-point compensation.
• Additional electrical resistance for heat pump, managed by regulation.
• Remote keypad with display.
• Clock board.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.


THAEY MODEL
Heating capacity kW
Absorbed power kW
C.O.P.
Heating capacity kW
C.O.P.
Cooling capacity kW
Absorbed power kW
E.E.R.
Sound pressure dB(A)
Silenced set up sound pressure dB(A)
Scroll/step compressor no.
Circuits no.
Buffer tank water content l
Circulator/standard electric pump nominal available head kPa
Electrical supply V-ph-Hz
DIMENSIONS AND WEIGHTS
L - PUMP width mm
W - TANK & PUMP width mm
H - Height mm
P - Depth mm
THAEY weight kg
SEASONAL ENERGY PERFORMANCE
THAEY MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW
SCOP (EN 14825)
ηs %
Energy class
122 127 130
23,5 30,3 34
7,94 10,16 11,25
2,96 3,02 3,02
24 30,9 34,5
3,75 3,80 3,72
22,7 26,7 29
7,99 10,23 11,84
2,84 2,64 2,45
52 53 53
49 50 50
1/1 1/1 1/1
1 1 1
45 45 45
64/131 61/116 57/112
400-3+N-50 400-3+N-50 400-3+N-50
122 127 130
1230 1535 1535
1522 1822 1822
1280 1510 1510
600 695 695
278 320 380
122 127 130
24 32 36
3,21 3,26 3,19
125 127 125
A+ A+ A+

Data at the following conditions:

Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.

Air: 7°C D.B. - 6°C W.B. - Water: 30/35°C.

Air: 35°C - Water: 12/7°C.

In open field (Q = 2) at 5 m from the unit.

Weight refers to most complete set up.

Performance according to EN 14511:2013. Set up with electric pump.

In Average climatic conditions, low temperature application (35°C)

Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/213 and No.813/2013)